Safebar General Specifications
SAFEBAR
100A Steel
150A Steel
160A Copper
250A Copper
400A Copper
Nominal Current
100amp
150amp
160amp
250amp
400amp
Intermittent Current
140amp
175amp
190amp
300amp
450amp
Cross Sectional Area
63mm
102mm
50mm
63mm
102mm
Resistance in Ohms
0.00187
0.00114
0.000370
0.000275
0.000169
Coefficient of Expansion
0.0000122
0.0000122
0.0000162
0.0000162
0.0000162
Max Temp for 100% Duty
25 Degrees
25 Degrees
25 Degrees
25 Degrees
25 Degrees
Insulation Shroud
PVC
PVC
PVC
PVC
PVC
Bar Length
4.5M
5M
4.5M
4.5M
5M
Hanger Support pitch
1.5M
2M
1.5M
1.5M
2M
Pitch btw Hangers
60mm
60mm
60mm
60mm
60mm
Pitch btw Cluster Hangers
40mm
40mm
40mm
40mm
40mm
Expansion section Above
130m
130m
130m
130m
130m
| SAFEBAR | 100A Steel | 150A Steel | 160A Copper | 250A Copper | 400A Copper | |
| Nominal Current | 100amp | 150amp | 160amp | 250amp | 400amp | |
| Intermittent Current | 140amp | 175amp | 190amp | 300amp | 450amp | |
| Cross Sectional Area | 63mm | 102mm | 50mm | 63mm | 102mm | |
| Resistance in Ohms | 0.00187 | 0.00114 | 0.000370 | 0.000275 | 0.000169 | |
| Coefficient of Expansion | 0.0000122 | 0.0000122 | 0.0000162 | 0.0000162 | 0.0000162 | |
| Max Temp for 100% Duty | 25 Degrees | 25 Degrees | 25 Degrees | 25 Degrees | 25 Degrees | |
| Insulation Shroud | PVC | PVC | PVC | PVC | PVC | |
| Bar Length | 4.5M | 5M | 4.5M | 4.5M | 5M | |
| Hanger Support pitch | 1.5M | 2M | 1.5M | 1.5M | 2M | |
| Pitch btw Hangers | 60mm | 60mm | 60mm | 60mm | 60mm | |
| Pitch btw Cluster Hangers | 40mm | 40mm | 40mm | 40mm | 40mm | |
| Expansion section Above | 130m | 130m | 130m | 130m | 130m |
Selection Guidlines
When selecting Liftco Safebar, first determine the electrical load requirements of the machinery
Secondly calculate the volt drop potential along the length of the system:
Volt drop = length x resistance x current x 1.73
When determining volt drop remember to take into account start up current demands which are higher than normal running currents
Consult relevent motor manufacturer specifications
Volt drop must not exceed 5% along the length of the system
To reduce volt drop the following options can be considered:
- Install a centre feed or multiple feeds
A centre feed effectively halves the length of the system
- Use a larger capacity Safebar or a Copper Safebar with low ressitance and high conductivity properties
Note that the ambient temperature, the heating of the conductor bar itself as a result of the duty cycle as well as the type of environment
can also influence the choice of Safebar required
Please consult the factory if in doubt as to volt drop requirements
A centre feed effectively halves the length of the system