Safebar General Specifications

office-bld

SAFEBAR 100A Steel 150A Steel 160A Copper 250A Copper 400A Copper
Nominal Current 100amp 150amp 160amp 250amp 400amp
Intermittent Current 140amp 175amp 190amp 300amp 450amp
Cross Sectional Area 63mm 102mm 50mm 63mm 102mm
Resistance in Ohms 0.00187 0.00114 0.000370 0.000275 0.000169
Coefficient of Expansion 0.0000122 0.0000122 0.0000162 0.0000162 0.0000162
Max Temp for 100% Duty 25 Degrees 25 Degrees 25 Degrees 25 Degrees 25 Degrees
Insulation Shroud PVC PVC PVC PVC PVC
Bar Length 4.5M 5M 4.5M 4.5M 5M
Hanger Support pitch 1.5M 2M 1.5M 1.5M 2M
Pitch btw Hangers 60mm 60mm 60mm 60mm 60mm
Pitch btw Cluster Hangers 40mm 40mm 40mm 40mm 40mm
Expansion section Above 130m 130m 130m 130m 130m

Selection Guidlines

When selecting Liftco Safebar, first determine the electrical load requirements of the machinery
Secondly calculate the volt drop potential along the length of the system:

Volt drop = length x resistance x current x 1.73

When determining volt drop remember to take into account start up current demands which are higher than normal running currents
Consult relevent motor manufacturer specifications
Volt drop must not exceed 5% along the length of the system

To reduce volt drop the following options can be considered:
  • Install a centre feed or multiple feeds
    A centre feed effectively halves the length of the system
  • Use a larger capacity Safebar or a Copper Safebar with low ressitance and high conductivity properties

Note that the ambient temperature, the heating of the conductor bar itself as a result of the duty cycle as well as the type of environment can also influence the choice of Safebar required

Please consult the factory if in doubt as to volt drop requirements